Transformer Leakage Reactance Determination by Test

S. K. Jain · International Journal of Electrical Engineering & Education · 1974

A method to determine separate values of primary and secondary leakage reactances of a transformer is given. An experimental determination of input impedance, open circuit time constant and dc resistance of one of the windings of the transformer, yields the required reactances.