AbstractResearches on the unit commitment with transmission network have been reported recently. However, most of these researches mainly discussed the security constrained unit commitment, while the relationship between unit commitment and transmission losses was not considered. However, from the standpoint of operating reserve for ensuring power supply reliability, a unit commitment considering transmission losses is required. Further, under the deregulation and liberalization of the electric power industry, not only the line's security but also transmission losses are expected to play an important role in calculating the network access charge, and unit commitment taking into account transmission losses is also desired from this viewpoint.In this paper, a unit commitment approach with both transmission losses and line flow constraint is presented. Based on a heuristic iterative optimization method, first, an initial schedule is created by using a successively decommitting unit approach that is proposed in this paper. Then, we determine constraints included in the unit commitment schedule by a heuristic iterative optimization approach, in which an algorithm able to get rid of line