Temperature distribution within an ACSR conductor during large current flow

Hiroshi Miyazaki, Satoshi Kitamura · Electrical Engineering in Japan · 2002

AbstractIn this paper, the temperature distribution within an ACSR conductor was precisely measured and examined, conducted as part of a series of studies on large currents in transmission lines. The study results may be summarized as follows: (1) The temperature difference within the conductor cross section increases as the square of the current; however, even at a current equal to 50% more than the allowable current, the maximum temperature difference within the aluminum components is from 5 °C (ACSR 410 mm2) to 6 °C (ACSR 810 mm2). (2) The results of measurements of the conductance between outer‐layer and inner‐layer aluminum strands in the conductor, and analysis of the current distribution in the inner and outer layers, indicated that even if the conductance were to drop sharply to 10,000 S/m, any inhomogeneity or concentration in the current distribution at a conductor connection joint has disappeared by 1.5 m or so from the tip of the joint. (3) According to measurements of the conductor temperature near a joint, the electrical resistance of the joint is lower than that of the same length conductor, so that the conductor temperature falls for 0.5 m or so from the tip of the